Case study / Multifamily residential property
Significant heating at the main neutral connection of a house panel supplying life safety equipment, including fire alarm circuits.
The situation
Inspection of house electrical systems for an apartment community, including the house panel supplying fire alarm and common area systems.
The finding
Significant heating at the main neutral connection of a house panel supplying life safety equipment, including fire alarm circuits.
The outcome
Documented and repaired. The repair was later verified. Fire alarm and exterior lighting circuits remained protected. The finding highlighted the importance of inspecting all connections, not just breakers.
Related industry: Multi-Family and Condos
Want Infinite Infrared to inspect your facility?
See how an electrical infrared inspection can help identify developing problems before they become outages or safety concerns.
Ready to find the problems before they find you?
See a real sample report, or request an inspection for your facility.
