Case study / Multifamily residential property

Significant heating at the main neutral connection of a house panel supplying life safety equipment, including fire alarm circuits.

Serious
FacilityMultifamily residential property
ScaleApartment community
EngagementAnnual infrared inspection
Max temp142.4°F
Delta T92.4°F

The situation

Inspection of house electrical systems for an apartment community, including the house panel supplying fire alarm and common area systems.

The finding

Significant heating at the main neutral connection of a house panel supplying life safety equipment, including fire alarm circuits.

The outcome

Documented and repaired. The repair was later verified. Fire alarm and exterior lighting circuits remained protected. The finding highlighted the importance of inspecting all connections, not just breakers.