Loose connection on an HVAC distribution panel feed

Abnormal heating on the B phase feed of a 480V HVAC distribution panel at a hotel, consistent with increased resistance at a connection.

PotentialHover or tap the image to compare the visual photo
EquipmentHVAC distribution panel
IndustryHospitality / Hotel
Problem typeLoose connection
Possible causeLoose Connection(s)
Maximum temperature110.3°F
Temperature rise35.3°F
Voltage480V
Ambient75°F
LoadApproximately 50% load

What was found

Thermal imaging identified abnormal heating on the B phase feed supplying HVAC equipment serving the hotel. Although the exact failure mechanism was not verified because repairs were performed by the client, the thermal pattern was consistent with increased resistance at the connection.

Why it mattered

This feed supplied HVAC equipment serving guest areas of the hotel.

Potential consequences

Loss of HVAC equipment could affect guest comfort and hotel operation.

Recommendation

Inspect, disassemble, clean and reassemble to proper component torque.