Loose connection on a hotel laundry distribution feeder

Significant heating on the A phase of a feeder supplying the hotel's laundry facilities, consistent with a loose and contaminated connection.

SeriousHover or tap the image to compare the visual photo
EquipmentLaundry distribution feeder
IndustryHospitality / Hotel
Problem typeLoose connection
Possible causeLoose Connection(s)
Maximum temperature146.9°F
Temperature rise68.1°F
Voltage480/277V
Ambient78.8°F
LoadA phase

What was found

The feeder supplying the hotel's laundry facilities exhibited abnormal heating.

Why it mattered

This feeder supplied the hotel's laundry facilities.

Potential consequences

Failure could interrupt washer and dryer operation, delaying housekeeping and affecting room turnover.

Recommendation

Inspect, disassemble, clean and reassemble to proper component torque.