Overloaded lighting circuit in a hotel kitchen

A 20A lighting circuit carrying approximately 18.5A in a hotel kitchen, flagged as Potential before the overloaded condition caused an outage.

PotentialHover or tap the image to compare the visual photo
EquipmentLighting circuit breaker
IndustryHospitality / Hotel
Problem typeOverload
Possible causeSuspect Overload
Maximum temperature108.8°F
Temperature rise29.8°F
Voltage120V
Ambient79°F
Load20A single pole breaker, approximately 18.5A measured load

What was found

This lighting circuit supplied the commercial kitchen inside a hotel. Although the thermal pattern was only classified as Potential, the circuit was operating at approximately 18.5 amps on a 20 amp breaker. Infrared testing identified the overloaded condition before an unexpected outage occurred.

Why it mattered

This circuit served the hotel's commercial kitchen, where reliable electrical supply supports food preparation and service operations.

Potential consequences

Failure could interrupt kitchen operations, affecting food preparation and guest service.

Recommendation

Check component rating versus circuit load. Upgrade or redistribute circuit load.